This website uses cookies that are essential to the operation of this site, to personalize content and allow us to analyze site performance. If you continue to use our website, you consent to the use of our cookies. Click OK to indicate your acceptance of our cookie policy, including advertising cookies, analytics cookies, and sharing of information with social media, advertising and analytics partners.

Learn more >

SmartSense Support

Helpful product guides, videos, and downloads to assist with the installation and troubleshooting of your dashboard.

SmartSense B Repeater Instructions for Use

The SmartSense B Repeater is designed to extend the range of an existing SmartSense B Sensor and can also act as an independent temperature sensor

Device Details

  • Can be paired to extend the range of an existing SmartSense B Sensor
  • Can act as an independent temperature sensor
  • Temperature information is broadcast at 10 minute intervals


Instructions for Use

  1. "RPTR" identifies the sensor as a repeater
  2. Remove the magnet from the face of the repeater
  3. Holding the repeater upside down will show the repeater state for 4 seconds
    • A flashing red LED indicates that no sensor is paired
    • A flashing green LED indicates the sensor is paired
  4. If held upside down longer than 4 seconds, the pairing process will begin
  5. The repeater will pair to the first found sensor that is in forced communication mode
  6. Steps for pairing a sensor to the repeater:
    • Start with the repeater and the sensor sitting on a flat surface, tab-side-up, for 60 seconds
    • Hold the sensor to be paired upside down until both LEDs begin to flash
      • Turn sensor right-side-up once LEDs begin to flash, then set on a flat surface
      • Sensor will remain in forced communication mode for 2 minutes
    • While sensor is in forced communication mode, hold the repeater upside down
      • The pairing process can take up to 60 seconds
      • At the end of the pairing process, the repeater will show its paired state
        • A flashing red LED indicates that no sensor is paired
        • A flashing green LED indicates a sensor is paired
  7. Steps for clearing a paired sensor:
    • Start with the repeater sitting on a flat surface, tab-side-up, for 60 seconds

    • Hold repeater upside down to start the pairing process
    • Continue holding the repeater upside down (tab down)
      • After approximately 30 seconds the repeater will clear the paired sensor information
      • A flashing red LED indicates that no sensor is paired

Best Practice Steps for Installation

  1. The best practice for walk-in units is to mount the sensor and/or repeater over the door seal (see examples)
    • Mounting the sensor and repeater in this orientation allows for the best broadcast transmission possible
  2. A typical use case scenario would be stacked walk-in units
    • This means you need to pass through the walk-in cooler to get to the walk-in freezer
  3. In the scenario of stacked walk-in units, the sensor and the repeater would be installed as follows:
    • Sensor and repeater need to be installed tab-side-up
    • Paired sensor mounted over the door seal in the walk-in freezer
    • Repeater sensor mounted over the door seal in the walk-in cooler
      • The repeater in the cooler receives the temperature broadcast from the freezer sensor
      • The repeater then re-broadcasts the freezer sensor information as well as supplies the temperature information for the cooler